WATERLESS R-454B Smart Logic Controller

Limit responsabilite nou
- Bon enstalasyon ak antretyen Ponp Chalè Total Green Mfg. la esansyèl pou bon pèfòmans li. Tout sistèm Total Green Mfg. yo dwe enstale epi antreteni pa yon kontraktè HVAC kalifye. Gwosè, seleksyon ak enstalasyon ekipman yo se responsablite sèl kontraktè enstalasyon an.
- Enstalasyon ekipman sou yon konsepsyon bouk latè an kwiv ki deja egziste ki pa koresponn ak yon konsepsyon bouk latè Total Green Mfg. aktyèl la pa otorize, sa ap anile tout garanti sou ekipman an, epi se responsablite sèl kontraktè enstalasyon an. Enstalasyon an dwe fèt dapre enstriksyon ki nan manyèl sa a. Si yon kontraktè HVAC kalifye pa fè enstalasyon an nan yon fason ki konsistan avèk manyèl sa a, sa ap anile epi anile pwoteksyon garanti limite pou sistèm nan.
- Total Green Mfg. pap responsab pou okenn defo, pèfòmans ki pa satisfezan, domaj oswa pèt, kit se dirèk oswa konsekansyèl, ki gen rapò ak konsepsyon, fabrikasyon, konstriksyon, aplikasyon oswa enstalasyon nenpòt konpozan espesifye nan chan an.
- All Total Green Mfg. forced air units will have separate terminal strips labeled “thermostat/zone board” and “air handler/furnace” for low voltage and are PLC “controlled.
- For proper equipment function, the thermostat or zone board must be tied to the “thermostat/zone board terminal” strip. The air handler or furnace must be tied to the “air handler/furnace” terminal strip. There will also be additional terminal strips for various functions based on the model type you may be working with. The information provided here is to supplement the installation manual specific to your unit.
- IMPORTANT: For WGxA, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.
WG1A Lè Fòse Sèlman – Lis fonksyon yo
- The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltagSi ou fèmen konpresè a epi ou mete l sou li ankò, sa re-inisyalize blokaj la toutotan switch tanperati dechaj la pa louvri. Switch tanperati dechaj la gen yon bouton re-inisyalizasyon manyèl. Yon switch tanperati dechaj ki louvri ap toujou mande yon re-inisyalizasyon manyèl ansanm ak yon bouton vòltaj ki ba.tagsik pouvwa a. Switch presyon yo otomatik.
- A “Y” call starts heating or cooling. A 20-minute timer will bring on AUX heat should that time elapse without having satisfied the heating call. Once aux. heat is called, aux. heat will stay called until the thermostat fully satisfies.
- Gen yon jumper enstale sou blòk tèminal fil elektrik ki make "A" ak "S". Avèk jumper la enstale, inite a ap fonksyone ak yon bann chofaj oksilyè jan li abitye. Si yo retire jumper la, PLC a antre nan mòd doub gaz, li kanpe konpresè a lè gen yon apèl pou chofaj oksilyè. Yon fwa apèl chofaj oksilyè a fini, yon revèy refwadisman 5 minit anpeche konpresè a rekòmanse sou yon apèl "Y" jiskaske tan an fini. Sa bay founo a tan pou l refwadi pou lè cho a pa lakòz yon presyon dechaj ki wo oswa yon blokaj lè konpresè a rekòmanse.
- Lè tèmosta a mete sou mòd refwadisman, siyal "O" a aktive valv ranvèsman an epi li bloke pwodiksyon chalè oksilyè a.
- Nan yon efò pou diminye konsomasyon enèji, PLC a koupe kouran aparèy chofaj karter la lè konpresè a ap mache.
- This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2A Lè Fòse Sèlman – Lis fonksyon yo
- The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to“X”. During this 60 second time period, the compressor will only operate in 1st stage giving the system a chance to recover before setting a hard lock out. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltagSi ou fèmen konpresè a epi ou mete l sou li ankò, sa re-inisyalize blokaj la toutotan switch tanperati dechaj la pa louvri. Switch tanperati dechaj la gen yon bouton re-inisyalizasyon manyèl. Yon switch tanperati dechaj ki louvri ap toujou mande yon re-inisyalizasyon manyèl ansanm ak yon bouton vòltaj ki ba.tagsik pouvwa a. Switch presyon yo otomatik.
- Yon apèl "Y1" kòmanse nan premye segonn nantagchofaj oswa refwadisman ki pral kontinye pandan 20 minit epi answit tan an rive nan 2yèm stagSi tan sa a ta dwe pase san tèmosta a pa rele "Y2". Si aparèy la an mòd chofaj, yon fwa 2yèm segonntage starts, a 20-minute timer will bring on AUX heat should that time elapse without having satisfied the heating call. Once all stagSi yo fin rele yo, y ap rete rele jiskaske tèmosta a satisfè nèt.
- Si gen plis pase 3 apèl "Y1" youn apre lòt san tèmosta a pa rele pandan 2yèm segonntagnan lespas 20 minit oubyen, anvan 20 minit dezyèm s latagLè revèy la fini, nan katriyèm apèl "Y1" la, yon sik antretyen kòmanse ki pral kenbe epi bloke sistèm nan nan yon 2èm segonn.tage for 5 minutes to assure oil return to the compressor. If the system is air zoned, a Zone Override terminal “D” will energize to 24 volts. As described in your unit installation manual, this 24-volt signal can be used along with a field supplied isolation relay to call open the largest zone and hold that damper open so the blower doesn’t see high static pressure during those 5 minutes. The maintenance cycle locks any other call out until completion. After the maintenance cycle, or if a “Y2” call is made before the maintenance cycle occurs, the
- counter resets back to zero. This makes our system zone friendly as it allows for true 2 stages chofaj ak refwadisman.
There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a
call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts. - Lè tèmosta a mete sou mòd refwadisman, siyal "O" a aktive valv ranvèsman an epi li bloke pwodiksyon chalè oksilyè a.
- Nan yon efò pou diminye konsomasyon enèji, PLC a koupe kouran aparèy chofaj karter la lè konpresè a ap mache.
- This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2AH Forced Air with Hydronic Heating Function
In addition to the function and features as described for WG2A units, The PLC program for the WG2AH units allows for switching priority call from forced air to hydronic heating as well as a feature called “Split Zone” that are installer optioned by choosing jumper settings as described below.
- Yo itilize yon kavalye sou bann tèminal fil elektrik ant tèminal "R" ak "AW" yo pou bay priyorite a chofaj lè a sou chofaj idwonik. Lè yo retire kavalye sa a, chofaj idwonik la vin tounen apèl priyorite a.
- Zòn Split la se yon karakteristik ki pèmèt ou chofe yon zòn oswa yon etaj ak chofaj idwonik epi yon lòt zòn oswa yon etaj ak lè fòse. Zòn Split la aktif lè w retire kavalye apèl priyorite a ki sou "R" ak "AW" epi w deplase l sou "R" ak "SZ" blòk tèminal fil elektrik la.
- Pandan l nan mòd "Zòn Separe", inite konpresè a ap bay chofaj lè fòse nan zòn lè a. Lè tank depo tanpon an mande chalè, inite konpresè a ap chanje pou chofe dlo. Si gen yon demann pou zòn lè a pandan inite konpresè a ap chofe dlo, demann lan ale dirèkteman nan sous chalè oksilyè a pou kenbe zòn lè a. Yon fwa tanperati tank la satisfè, sistèm nan retounen nan chofaj lè nòmal ak inite konpresè a.
- When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, the water pumps starts to establish good water flow. 30 seconds after that stage, the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
- Fonksyon chofaj idwonik la enfim nenpòt lè tèminal "O" a resevwa enèji, sa ki mete inite a nan mòd refwadisman.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2AD Lè fòse ak fonksyon chofaj dlo domestik
Anplis fonksyon ak karakteristik jan sa dekri pou inite WG2A yo jan sa dekri nan premye seksyon dokiman sa a, pwogram PLC pou inite WG2AD yo pèmèt chanje apèl priyorite soti nan lè fòse pou ale nan chofaj dlo domestik.
- Yo itilize yon kavalye sou bann tèminal fil elektrik ant tèminal "R" ak "AW" yo pou bay priyorite a chofaj/refwadisman lè a sou chofaj dlo domestik. Lè yo retire kavalye sa a, chofaj dlo domestik la vin tounen apèl priyorite a.
- When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, the water pumps starts to establish good water flow. 30 seconds after that stage, the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
- Yon karakteristik PLC fonksyonèl siplemantè ki eksklizif nan modèl WG2AD la ki pèmèt dlo chofe jiska 120 degre, se kapasite inite a pou kenbe estabilite konpresè a lè li diminye chaj konpresè a jan sa nesesè pou kontwole presyon dechaj la.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
Kontwolè lojik entelijan
WG1H 100% Idwonik Chofe ak Dlo Refwadi Sèlman – Lis fonksyon yo
- PLC a verifye si switch presyon BA/WO, tanperati HX Ba ak tanperati dechaj yo byen fèt. Yon antre switch sekirite ouvè gen yon reta 60 segonn anvan li mete yon siyal blokaj ak fay sou "X". Sa a se pou anpeche apèl anmèdan, espesyalman nan kòmansman sezon refwadisman an lè Bouk Latè yo pi frèt. "X" la mete ak nenpòt kondisyon blokaj fò. Vire bouton presyon ba a.tagSi ou fèmen konpresè a epi ou mete l sou li ankò, sa re-inisyalize blokaj la toutotan switch tanperati dechaj la pa louvri. Switch tanperati dechaj la gen yon bouton re-inisyalizasyon manyèl. Yon switch tanperati dechaj ki louvri ap toujou mande yon re-inisyalizasyon manyèl ansanm ak yon bouton vòltaj ki ba.tagsik pouvwa a. Switch presyon ak tanperati ba HX yo otomatik.
- Yon apèl "N" demarre ponp sikilatè a pandan 30 segonn anvan konpresè a pou pèmèt yon koule konplè nan HX (echanjeur chalè) anvan konpresè a demarre. Yon fwa apèl la fini, ponp lan ap fonksyone pandan 30 segonn anplis apre konpresè a fin sispann pou retire nenpòt chalè ki rete nan HX la. Sa rive kèlkeswa si se yon apèl dlo chofe oswa dlo frèt.
- If the compressor unit sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor. The “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
Si ou gen nenpòt kesyon konsènan nenpòt nan fonksyon sa yo, tanpri kontakte Total Green Mfg. nan 419-678-2032 pou sipò teknik.
Kesyon yo poze souvan
- Q: Can I use any thermostat with the Smart Logic Controller?
A: Yes, the PLC program allows for the use of almost any heat/cool thermostat, but Total Green Mfg. recommends using Honeywell 8000 series thermostats for optimal performance.
Dokiman / Resous
![]() |
WATERLESS R-454B Smart Logic Controller [pdfGid Enstalasyon R-454B, WGxA, WG2AH, WG2AD, R-454B Smart Logic Controller, R-454B, Smart Logic Controller, Logic Controller, Controller |