Synapse CSEN1 Combo Sensor Controller Installation Guide

Synapse CSEN1 Combo Sensor Controller - Featured Image

Synapse - logo

ENSTALE GID
CSEN1

CSEN1 Combo Sensor Controller

Synapse CSEN1 Combo Sensor Controller

Part Numbers: CSEN1-H-W-ZHA (white enclosure) and CSEN1-H-G-ZHA (gray enclosure)

DESKRIPSYON

The CSEN1 is a low voltage Networked Lighting Controller with an integrated passive infrared sensor and a photocell. It is powered via the AUX power from the LED driver. The CSEN1 autodetects both 0-10V Drivers and D4i Drivers to simplify the installation. The product is DLC certified for both indoor and outdoor applications.

SPECIFICATIONS

  • Frekans radyo: 2.4 GHz (IEEE 802.15.4)
  • RF Transmisyon Sorti pouvwa: +20dBM
  • Tanperati Fonksyònman: -40 ° a + 70 ° C
  • Imidite fonksyònman: 10 a 95%, ki pa kondanse
  • IP66 Rated patiraj
  • Dimansyon: 3.1 "D x 1.6" H (80mm D x 42mm H)
  • Input Power: 12-24VDC, 35mA max, 840mW
  • Objektif kontwòl: opere
  • Environmental: Indoor/Outdoor
  • Degre polisyon: 3
  • Rated Impulse Voltage: 330V

KONSIDERAsyon DESIGN

Below are some recommendations for successful analog dimming using the CSEN1. The analog dimming control wires are referenced as DALI+/DIM+ and Common Ground/DALI-. The dimming signals have a Maximum voltage nan 10V DC.

  • Do not ground the Common Ground/DALI- wire to chassis ground; this is a return signal and is critical for proper dimming.
  • Wout fil gradyasyon lwen liy AC si sa posib.
  • Maksimòm 4 chofè DALI-2/D4i ki ap dirije pou chak kontwolè, konsilte sipò Synapse si yo bezwen yon pi gwo rapò.
  • Maximum of 8 DIM to OFF LED Drivers for DIM to OFF Designs.
  • Pa monte sou yon chalè oswa sou yon chofè ki ap dirije.

REMAK: Chofè LED dwe sipòte DIM pou OFF fonksyonalite.
AVÈTISMAN AK ATANSYON

  • TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE INSTALLING OR SERVICING!
  • The CSEN1 should only be installed in a fixture with a Zhaga Book 18 receptacle.
  • Si w pa suiv enstriksyon ak avètisman sa yo, sa ka anile garanti a.
  • This product must be installed in accordance with national, state, and local electrical codes and requirements.
  • If you are unsure about any part of these instructions, consult an electrician; qualified personnel should perform all work.

DETAY KABÒSYON ZHAGA BOOK 18 SOCKET

TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE INSTALLING OR SERVICING!
For fixtures with an existing Zhaga socket, prior to installation, verify the wiring per the details below. (See Figure 1) If the fixture does not have a Zhaga socket, use the appropriate Wired Adapter accessory based on the knockout size: CSEN1-ZHA-ADPT-22 for 22mm knockouts, or CSEN1-ZHA-ADPT-33 for 33mm knockouts. The specifications for the signal wires are:

  • 12-24VDC POWER: Brown
  • Common Ground/DALI-: Pink with White Stripe
  • DALI+/DIM+: Violet with White Stripe
  • Solid Conductor, 105°C, Rated for 600VAC, AWG 20, 15” Length

Figi 1 Synapse CSEN1 Combo Sensor Controller - FIGURE 1

ENSTRIKSYON ENSTALASYON

TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE INSTALLING OR SERVICING!

  1. Si sa aplikab, retire bouchon an sele oswa aparèy kontwòl ekleraj ki enstale kounye a nan reseptak aparèy la.
  2. Align the CSEN1 such that the contacts pins are positioned at the appropriate the receptacle contacts.
  3. After alignment, push until the CSEN1 is fully seated within the receptacle.
  4. While pushing against the device, twist the CSEN1 housing clockwise until it locks into place. The CSEN1 includes a latching key or notch that will lock into position with an audible “click”. (See Figure 2)

Nòt: Pou fonksyone byen, asire w ke kontwolè a antre nèt nan priz la ak trese nan pozisyon an fèmen.
Avètisman: The Zhaga receptacle should not turn during installation. Turning the receptacle could damage the internal fixture wiring by pulling it loose.
Figi 2Synapse CSEN1 Combo Sensor Controller - FIGURE 2

LEDS STATUS

Pouvwa ki ap dirije Estati 
Ble On for 3 seconds at Startup, then Off
Ki ap dirije estati Estati 
Wouj No script on the device
Koulè wouj Erè kominikasyon
Klè ble Communication, No Config
Klike vèt Normal Operation with Motion
Off Normal Operation, no Motion

ENFÒMASYON AK SÈTIFIKASYON REGLEMAN
RF Exposure Statement: This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance of 20cm between the radiator and your body. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
Sètifikasyon Industry Canada (IC): Aparèy dijital sa a pa depase limit Klas B pou emisyon bri radyo ki soti nan aparèy dijital ki tabli nan Règleman Entèferans Radyo Depatman Kominikasyon Kanadyen an.
Sètifikasyon FCC ak enfòmasyon regilasyon (USA sèlman)
FCC Pati 15 Klas B: Aparèy sa a konfòm ak pati 15 règleman FCC yo. Operasyon an sijè a de kondisyon sa yo: (1) Aparèy sa yo pa ka lakòz entèferans danjere, epi (2) Aparèy sa yo dwe aksepte nenpòt entèferans resevwa, enkli entèferans ki ka lakòz operasyon danjere.
RADIO FREQUENCY INTERFERENCE (RFI) (FCC 15.105): This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: (1) Re-orient or relocate the receiving antenna; (2) Increase the separation between the equipment and the receiver; (3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected; (4) Consult the dealer or an experienced radio/TV technician for help.
Declaration of Conformity (FCC 96-208 & 95-19): Synapse Wireless, Inc. declares that the product name CSEN1 to which this declaration relates, meet the requirements specified by the Federal Communications Commission as detailed in the following specifications:

  • Pati 15, Sous-pati B, pou ekipman Klas B
  • FCC 96-208 jan li aplike pou klas B òdinatè pèsonèl ak periferik
  • Yo te teste pwodui sa a nan yon laboratwa tès ekstèn ki sètifye dapre règleman FCC epi yo jwenn li satisfè limit emisyon FCC, Pati 15. Dokimantasyon an sou file ak disponib nan Synapse Wireless, Inc.

Si FCC ID pou modil la andedan patiraj pwodui sa a pa vizib lè enstale andedan yon lòt aparèy, Lè sa a, deyò aparèy la kote pwodui sa a enstale dwe montre tou yon etikèt ki refere a modil FCC ID ki fèmen. Modifikasyon (FCC 15.21):
Chanjman oswa modifikasyon nan ekipman sa a ki pa ekspreseman apwouve pa Synapse Wireless, Inc., ka anile otorite itilizatè a pou opere ekipman sa a.
Patante - mak vityèl nan https://www.synapsewireless.com/about/patents
Pou aprann plis vizite: synapsewireless.com

SÈTIFIKASYON

Modèl CSEN1-H-W-ZHA (white enclosure) or CSEN1-H-G-ZHA (gray enclosure)
Gen ID FCC QOQ-GM240P
Gen IC 5123A-GM240P
RoHS NAN 2011/65/EU (2015/863)
Inyon Ewopeyen REACH (EC) No 1907/2006

DALI-2 Sètifye Aplikasyon Kontwolè

Synapse - logoSynapse CSEN1 Combo Sensor Controller - icon

 

Dokiman / Resous

PDF thumbnailCSEN1 Combo Sensor Controller
Installation Guide · CSEN1-H-W-ZHA, CSEN1-H-G-ZHA, CSEN1 Combo Sensor Controller, CSEN1, Combo Sensor Controller, Sensor Controller, Controller

Referans

Poze yon Kesyon

Use this section to ask about setup, compatibility, troubleshooting, or anything missing from this manual.

Poze yon Kesyon

Ask about setup, compatibility, troubleshooting, or anything missing from this manual. Name and email are optional.