BSEED W-SD Multi Function Power Meter

fonksyon kle

Entwodiksyon pwodwi
The multi – functional Wlfl guide rail meter adopts a rail – type design, which is small in size, compact instructure and simple in installation; it uses an LCD display screen to display current, voltage, electricity, power,frequency and other electrical parameters, is convenient for users to acquire data and easy to operate. It hasgood anti – electromagnetic interference capabilities, meets various needs of power management, facilitates therealizationof terminal – intelligent power metering, and facilitates the retrofitting of power meters in the lateltransformation of the lighting system. It is widely used in commercial squares, science and technology parksuniversities and other occasions where billing is required, It can also be jointly deployed with energyconsumption monitoring and energy management systems. its application scope includes property bilingmanagement, electricity metering, power demand – side management, energy management andenergy-saving analysis, Other low – voltage power systems, etc.
Paramèt teknik
| rated voltage | AC 220V/110v |
| Opere voltage ranje | AC 80V-300V |
| Frekans | 50/60Hz |
| Ranje pouvwa | 0-99999kwh |
| Ranje distribisyon | 0-999 jou |
| Faktè pouvwa | 0-1.0PF |
| Ranje tanperati | -40-150°C |
| Overvoltage ranje anviwònman | 130-300V |
| Undervoltage ranje anviwònman | 75-21ov |
| Ranje paramèt surkouran | 1-63A |
| Overpower setting range | 1-15KW |
| Rated izolasyon voltage | 400V |
| Sòti kontak | 1NO |
| Lavi mekanik | 10,000 fwa |
| Klas pwoteksyon | lp30 |
| Altitid | ::,2000m |
| Imidite | 550%at40°C(non-condensing) |
Function Introduction, Default Settings
| Opsyon | Anviwònman ranje | Paramèt default |
| Overvoltage
pwoteksyon |
230-300V | 270V |
| Undervoltage
pwoteksyon |
110-21ov | 170V |
| Surkouran
pwoteksyon |
0.1-63A | 40A |
| Pwoteksyon Surcharge | 1-15KW | 8. 8KW |
| Enèji elektrik
pwoteksyon |
0-99999kwh | 99999kwh |
| Siperyè
pwoteksyon |
0-150°( | 85°C |
| Number of closures | 1-30 fwa | 5 fwa |
| Closingtime | 1-600 segonn | 30 segonn |
| Electricityclearing | Sou / Off | koupe |
| Timing clearing | Sou / Off | koupe |
| Power-up operation | Close/open/hold | kenbe |
| Overvoltagedelay
pwoteksyon |
1-600 sec/off | koupe |
| Undervoltagedelay
pwoteksyon |
1-600 sec/off | koupe |
| Overcurrent delay
pwoteksyon |
1-600 sec/off | koupe |
| Overloaddelay
pwoteksyon |
1-600 sec/off | koupe |
| Siperyè
delayprotection |
1-600 sec/off | koupe |
structural analysis

DIMANSYON
Gwosè pwodwi

Dyagram fil elektrik

Set function operation
Press the set key for 5 seconds to enter the settings page, give an example of the “Overvoltage Protection” setting, click the
key cursor to move to the “Overvoltage Protection” position, press the set key to select, press the
key to adjust to the required value, press the set to save after the adjustment is completed, and press the
key to select other settings. If you do not need to set it, press the
key to move the cursor to the exit position, and then press set to return to the home page. The other settings can be the same as the “Overvoltage Protection” setting method.
Set function operation
Download Smart lavi APP
or Graffiti APP Smart Connection
WIFI connection or reset operation method: Long press the wifi key 5-10s wifi indicator light will flash, turn on the phone Bluetooth, then open the Smart Life APP, click “+” in the upper right corner, select “Add Device”, wait for the device to scan out the device, click on the device to select the wifi name, enter the password to wait for the device to be added successfully.
PLIS ENFÒMASYON

Dokiman / Resous
![]() | W-SD Multi Function Power Meter |
Referans
- Manyèl itilizatèmanual.tools