Entwodiksyon
This manual provides comprehensive instructions for the safe and efficient operation, setup, and maintenance of the Elitech Digital Manifold Gauge Set, model DMG-2SE. This device is designed for precise measurement of pressure and temperature in HVAC, refrigeration, and air conditioning systems. Please read this manual thoroughly before use to ensure proper functionality and safety.
Enfòmasyon sou Sekirite
- Always wear appropriate personal protective equipment (PPE), including safety glasses and gloves, when handling refrigerants.
- Ensure all hose connections are secure and leak-free before applying pressure or vacuum to a system.
- Do not exceed the maximum working pressure of the hoses (500 PSI) or the gauge (800 PSI). Exceeding these limits can cause equipment damage or personal injury.
- Use the device in a well-ventilated area to prevent the accumulation of refrigerant vapors.
- Refer to local and national regulations for proper refrigerant handling, recovery, and disposal procedures.
- Keep the device away from moisture, direct sunlight, and extreme temperatures to prevent damage to electronic components.
- Pa eseye demonte oswa modifye aparèy la. Konfye tout antretyen bay pèsonèl kalifye.
Pwodwi souview ak Konpozan
The Elitech DMG-2SE is a digital manifold gauge designed for HVAC/R professionals, offering accurate pressure and temperature measurements. It features a high-definition LCD screen, intuitive controls, and robust construction for reliable performance.



Kawoutchou frigorigènes
The included refrigerant charging hoses are color-coded for easy identification and proper connection.


Espesifikasyon
- Ranje presyon: -14 a 800 psi
- Presizyon: ±1% FS (Full Scale)
- Rezolisyon: 1 psi
- Inite presyon: psi, kg/cm², kPa, MPa, bar, inHg
- Inite Tanperati: ° C / ° F.
- Refrijeran konpatib: Supports 88 types (e.g., R11, R12, R22, R134a, R410a, R404a, R407c, R507, R32, R290, R600a, R1234yf, etc.). The device defaults to 18 types and can be updated via an app.
- Longè kawotchou: 59 pous (1.5m)
- Koneksyon kawotchou: 1/4" SAE
- Hose Working Pressure: 500 PSI (Yellow, Blue, Red)
- Hose Burst Pressure: 4000 PSI (Yellow, Blue, Red)
- Pouvwa: 2 x AAA batteries (replaceable)
- Lavi batri: Apeprè 200 èdtan
- Dimansyon: Approximately 4.3 inches (11 cm) width, 5.3 inches (13.5 cm) height, 2.9 inches (7.4 cm) depth.
- Pwa: Apeprè 1.5 liv (680g)
Enstalasyon
- Enstalasyon batri: Open the battery compartment located on the back of the unit. Insert two AAA batteries, ensuring correct polarity (+/-). Close the compartment securely.
- Premye pouvwa sou: Peze bouton pouvwa a (U symbol) to turn on the device. The LCD screen will illuminate.
- Seleksyon inite: Use the "MODE" button to cycle through available measurement units (psi, kg/cm², kPa, MPa, bar, inHg for pressure; °C/°F for temperature). Select your preferred units by stopping on the desired option.
- Refrigerant Selection: Press the "MODE" button repeatedly until the refrigerant type (e.g., R134a) flashes on the display. Use the up/down arrow buttons to scroll through the list of supported refrigerants. Confirm your selection by pressing "MODE" again or by waiting a few seconds for the selection to auto-confirm.
- Zeroing the Pressure: Before connecting the gauge to any system, ensure it is at atmospheric pressure (not connected to any pressure source). Press the "ZERO" button to calibrate the pressure reading to zero. This ensures accurate measurements.
Enstriksyon Operasyon
Konekte kawotchou yo
- Konekte a blue hose to the low-pressure service port of the HVAC/R system.
- Konekte a red hose to the high-pressure service port of the HVAC/R system.
- Konekte a yellow hose to the service port of your vacuum pump, refrigerant tank, or recovery machine.
- Ensure all connections are hand-tightened, then slightly snugged with a wrench to prevent refrigerant leaks.
Measuring Pressure and Temperature
- With the hoses connected to the system, slowly open the appropriate valve knobs on the manifold gauge to allow system pressure to reach the internal sensors.
- The LCD will display real-time pressure readings for both the high and low sides of the system.
- Simultaneously, the display will show the corresponding saturation temperatures (evaporation and condensation temperatures) for the currently selected refrigerant.
- The "PT" (Pressure-Temperature) mode shows pressure and saturation temperature. "Ev" (Evaporation) and "Co" (Condensation) indicate the saturation temperatures, while "PL" (Low Pressure) and "PH" (High Pressure) indicate the actual system pressures.

Refrigerant Charging/Recovery
The DMG-2SE provides accurate pressure readings essential for refrigerant charging and recovery processes. Always follow industry best practices and local regulations for these operations.
- Pou chaje: Connect the yellow hose to the refrigerant tank. Purge any air from the yellow hose before opening the manifold valve to the system. Monitor the pressure readings on the DMG-2SE to ensure the correct charge is added.
- For Recovery: Connect the yellow hose to a certified refrigerant recovery machine. Follow the recovery unit's instructions and monitor system pressures on the DMG-2SE during the recovery process.
Antretyen
- Netwayaj: Siye aparèy la ak yon mou, damp cloth. Do not use abrasive cleaners, solvents, or immerse the unit in water.
- Ranplasman batri: Replace batteries when the low battery indicator appears on the display. Ensure the device is powered off before opening the battery compartment and replacing the two AAA batteries.
- Enspeksyon kawotchou: Regularly inspect all refrigerant hoses for signs of wear, cracks, cuts, or damage. Replace damaged hoses immediately to prevent refrigerant leaks and ensure safety.
- Depo: Store the manifold gauge set in a clean, dry place, away from direct sunlight, extreme temperatures, and corrosive environments.
Depanaj
| Pwoblèm | Kòz posib | Solisyon |
|---|---|---|
| Aparèy pa limen | Batri ki mouri oswa mal enstale | Ranplase pil yo, asire w ke polarite a kòrèk. |
| Lekti presyon ki pa kòrèk | Gauge not zeroed; Leaking connections; Incorrect refrigerant selected | Zero the gauge before use. Check all hose connections for leaks. Verify the correct refrigerant type is selected. |
| Ekran an montre "Err" | Sensor error or measurement out of range | Power off and restart the device. If the error persists, contact customer support. |
Garanti ak sipò
For detailed warranty information, technical support, or service inquiries regarding your Elitech Digital Manifold Gauge Set DMG-2SE, please contact Elitech customer service. Refer to the product packaging or the official Elitech websit la pou jwenn enfòmasyon kontak ak resous sipò ki pi resan yo.