Entwodiksyon
The AEMC Model 3711 is a portable clamp-on ground resistance tester designed for measuring electrical ground rod and grid resistance in multi-grounded systems. This instrument offers a non-intrusive method for testing without the need for auxiliary rods or disconnecting the ground system. It also measures leakage, neutral, and phase currents, providing a comprehensive solution for electrical system analysis.
Enfòmasyon sou Sekirite
AVÈTISMAN: Always read and understand all safety instructions before operating this instrument. Failure to do so may result in serious injury or death.
- This instrument is rated CAT III, indicating its suitability for measurements in building installations.
- Adhere to all local and national safety codes and regulations.
- Do not use the instrument if it appears damaged or is operating abnormally.
- Asire w ke konpatiman batri a byen fèmen anvan w itilize li.
- Evite kontak ak sikui aktif yo pandan mezi a.
- The instrument is double-insulated for enhanced safety.
Ki sa ki nan bwat la
Verifye ke tout atik yo prezan lè w ap debale yo:
- AEMC Ground Resistance Tester Model 3711
- Calibration Check Loop, 25Ω
- Hard Ka Pote
- 9V batri alkalin
- Manyèl Itilizatè (dokiman sa a)
Pwodwi souview

Image: The AEMC Model 3711 Clamp-On Ground Resistance Tester. This image displays the device with its red clamp jaws open, a black body, and a green digital display showing "9.8 Ω". Control buttons are visible below the display.
The AEMC Model 3711 features an ergonomic design for one-handed operation. Its robust polycarbonate construction ensures durability for outdoor use. Key components include:
- Clamp Machwa: 1.25" opening to accommodate ground rods and cables up to 1000kcmil.
- Ekspozisyon LCD: Digital readout for resistance and current measurements.
- Bouton kontwòl: For power, data hold, and mode selection.
- Lòj batri: Located at the rear for a 9V battery.
Enstalasyon ak Enstalasyon Batri
- Open the battery compartment cover on the rear of the instrument.
- Insert the supplied 9V Alkaline battery, observing correct polarity.
- Fèmen kouvèti lòj batri a byen.
- Press the "ON" button to power on the device. The display should illuminate.
Enstriksyon Operasyon
Ground Resistance Measurement
- Power on the AEMC 3711.
- Louvri cl laamp jaws by pressing the release lever.
- Mete cl laamp around the ground conductor or rod to be tested, ensuring the jaws are fully closed.
- The instrument will automatically measure and display the ground resistance in Ohms (Ω).
- For stable readings, allow approximately one second for the measurement to settle.
- To hold the current reading on the display, press the "HOLD" button. Press again to release.
Aktyèl Mezi
- Power on the AEMC 3711.
- Louvri cl laamp machwè.
- Mete cl laamp around the conductor carrying the current to be measured (leakage, neutral, or phase current). Ensure the jaws are fully closed.
- The instrument will automatically measure and display the current in Amperes (A) oswa milliAmperes (mA).
- The current measurement function provides direct readings for leakage current flowing to ground or circulating in ground loops (down to 1mA) and neutral/phase currents (up to 30A RMS).
Antretyen ak Kalibrasyon
Netwayaj
Netwaye enstriman an ak yon mou, damp twal. Pa sèvi ak pwodui netwayaj abrazif oswa solvang.
Ranplasman batri
When the low battery indicator appears on the display, replace the 9V battery as described in the "Setup and Battery Installation" section.
Kalibrasyon Tcheke
Use the supplied 25Ω calibration check loop to verify the instrument's accuracy periodically. Clamp the tester around the loop; the reading should be approximately 25Ω. If the reading deviates significantly, contact AEMC customer support for service.
Depo
Store the instrument in its hard carrying case in a dry, cool environment when not in use. Remove the battery if storing for extended periods.
Depanaj
- No Display/Instrument Not Powering On: Tcheke enstalasyon batri a epi asire w ke batri a gen ase chaj. Ranplase l si sa nesesè.
- Lekti enstab: Asire clamp jaws are fully closed around the conductor. Verify there is no excessive electrical noise in the environment.
- "OL" oswa Endikasyon Surcharge: The measured value exceeds the instrument's range. Ensure the correct measurement function is selected or the circuit parameters are within the device's limits.
- Lekti ki pa kòrèk: Perform a calibration check using the 25Ω loop. If the issue persists, contact technical support.
Espesifikasyon
| Paramèt | Valè |
|---|---|
| Ranje Rezistans Tè | Autoranging 0.01 to 1200Ω |
| Ranje Mezi aktyèl | Autoranging 1mA to 30.00A RMS |
| Resistance Measuring Frequency | 2403Hz |
| Current Measuring Frequency | 47 a 800Hz |
| Accuracy (Resistance) | ±2% reading ±0.02Ω (up to 25% of reading for 600-1200Ω) |
| Tanperati Fonksyònman | -10 a 55 ° C (14 a 131 ° F) |
| Sous pouvwa | 9V batri (enkli) |
| Pwa | 1kg (2.2lbs) |
| Dimansyon (H x W x P) | 235 x 100 x 55mm (9.25 x 3.94 x 2.17 pous) |
| Ouvèti machwè | 1.25 pous |
| Evalyasyon Sekirite Sosyal | EN 61010, CAT III, UL approved, CE marked |
Garanti ak sipò
For warranty information, technical support, or service inquiries, please refer to the official AEMC Instruments websit la oubyen kontakte depatman sèvis kliyan yo. Kenbe resi acha w la pou reklamasyon garanti.