Entwodiksyon
This manual provides essential information for the safe and effective use of the YASKAWA V1000 Series AC Drive, model CIMR-VU4A0011FAA. The V1000 is a compact, high-performance variable frequency drive designed for a wide range of industrial applications, offering precise motor control and energy efficiency. Please read this manual thoroughly before installation, operation, or maintenance.

Figure 1: Yaskawa V1000 AC Drive, showing the main unit with its grey casing and heat sink fins.
Enfòmasyon sou Sekirite
Always observe the following safety precautions to prevent injury, damage to equipment, or property loss. This drive contains high voltage components and should only be handled by qualified personnel.
- Danje elektrik: Ensure all power is disconnected and verified before performing any installation, wiring, or maintenance. Wait for the charge indicator to extinguish.
- Atè: Properly ground the drive and motor according to local electrical codes.
- Pèsonèl ki kalifye: Installation, operation, and maintenance must be performed by trained and qualified personnel only.
- Kondisyon anviwònman: Do not expose the drive to moisture, corrosive gases, or excessive dust. Operate within specified temperature and humidity ranges.
- Ijans Stop: Always install an independent emergency stop circuit.
Enstalasyon
1. Debalaj ak Enspeksyon
Carefully remove the drive from its packaging. Inspect the unit for any signs of damage that may have occurred during shipping. Verify that all components listed in the packing list are present.

Figure 2: The Yaskawa V1000 AC Drive unit shown alongside its accompanying instruction manual, still in its plastic packaging.
2. Monte
Mount the drive vertically on a flat, stable surface. Ensure adequate clearance for ventilation around the unit. Refer to the dimensions provided in the specifications section for proper spacing. Avoid mounting in direct sunlight or near heat sources.
3. fil elektrik
All wiring must comply with national and local electrical codes. Use appropriate wire gauges for power, motor, and control circuits. Ensure proper grounding of the drive chassis and motor frame.
- Power Input (R/L1, S/L2, T/L3): Connect the three-phase AC power supply.
- Motor Output (U/T1, V/T2, W/T3): Konekte ak tèminal motè yo.
- Tèminal kontwòl: Connect external control signals (e.g., start/stop, speed reference, fault outputs) as required by your application.

Figi 3: Anba view of the Yaskawa V1000 AC Drive, showing the heat sink fins and mounting points, crucial for proper ventilation and installation.
4. Premye Limen
Before applying power, double-check all wiring connections. Ensure no loose wires or foreign objects are present. Apply power and observe the drive's display. The drive should power on and display its default status or a ready message.
Opere
1. Operasyon debaz
The V1000 drive can be operated via its built-in keypad, external control terminals, or serial communication. For basic operation using the keypad:
- Peze a KOURI bouton pou kòmanse motè a.
- Peze a SISPANN bouton pou kanpe motè a.
- Sèvi ak la MWEN / DESANN arrow keys to adjust the output frequency (motor speed) if in frequency reference mode.
2. Paramèt Anviwònman
The drive's behavior is configured through various parameters. Access the parameter menu via the keypad. Key parameters include:
- A1-01 (Control Method Selection): Select V/f control, Sensorless Vector Control, etc.
- B1-01 (Motor Rated Current): Input the motor's full load current.
- C1-01 (Acceleration Time): Set the time for the motor to accelerate from 0 Hz to maximum frequency.
- C1-02 (Deceleration Time): Set the time for the motor to decelerate from maximum frequency to 0 Hz.
Refer to the comprehensive parameter list in the full YASKAWA V1000 technical manual for detailed descriptions and settings.
Antretyen
Regular maintenance ensures optimal performance and extends the lifespan of your V1000 AC Drive. Always disconnect power before performing any maintenance.
- Netwayaj: Periodically clean the drive's exterior and ventilation openings to prevent dust accumulation, which can impede cooling. Use a soft, dry cloth. Do not use solvents.
- Enspeksyon fanatik: Check cooling fans for proper operation and cleanliness. Replace fans if they are noisy, vibrating excessively, or not rotating freely.
- Sere Tèminal: Annually check the tightness of all power and control terminal screws. Loose connections can cause overheating and damage.
- Lavi kondansateur: Electrolytic capacitors have a finite lifespan. Consider replacement after 5-10 years of continuous operation, depending on environmental conditions.
Depanaj
This section provides guidance for common issues. For detailed fault codes and advanced troubleshooting, consult the full YASKAWA V1000 technical manual.
| Sentòm | Kòz posib | Aksyon Korektif |
|---|---|---|
| Kondwi a pa limen | Pa gen kouran antre; Fuzib boule; Pwoblèm entèn | Check power supply; Inspect fuses; Contact support if internal fault suspected. |
| Motè pa mache | Incorrect wiring; Parameter settings; External stop signal active | Verify wiring (motor/control); Check parameter settings (e.g., frequency reference, run command source); Ensure no active stop signals. |
| Overcurrent fault (OC) | Motor overload; Short circuit in motor/cables; Rapid acceleration/deceleration | Check motor load; Inspect motor and cables for damage; Increase acceleration/deceleration times. |
| Overvoltagfòt e (OV) | Regenerative energy from motor; High input voltage | Increase deceleration time; Install braking resistor if necessary; Verify input voltage. |
Espesifikasyon
Key technical specifications for the YASKAWA V1000 AC Drive, model CIMR-VU4A0011FAA:
| Paramèt | Valè |
|---|---|
| Nimewo Modèl | CIMR-VU4A0011FAA |
| Antre Voltage | AC 3-Phase 380-480V |
| Antre frekans | 50/60 Hz |
| Input Current (Rated) | 14.0A (380V) / 10.4A (480V) |
| Sòti Voltage | AC 3-Phase 0-480V |
| Sòti yo itilize souvan Kalite | 0-400 Hz |
| Output Current (Rated) | 11.1A (380V) / 9.2A (480V) |
| Mass / Weight | 2.6 kg (apeprè 5.73 lbs) |
| Evalyasyon patiraj | IP20 |
| Manifakti | YASKAWA |
| Peyi orijin | Japon |
| ASIN | B008HQ5TP0 |

Figure 4: Detailed product label of the Yaskawa V1000 AC Drive, displaying the model number, input/output electrical ratings, and manufacturing information.
Garanti ak sipò
YASKAWA products are manufactured to high standards and typically come with a manufacturer's warranty. For specific warranty terms and conditions, please refer to the warranty documentation included with your purchase or visit the official YASKAWA websit.
For technical support, service, or to inquire about replacement parts, please contact YASKAWA customer service or an authorized YASKAWA distributor. Provide your product model number (CIMR-VU4A0011FAA) and serial number when seeking assistance.
You can find more information and contact details on the official YASKAWA websit: www.yaskawa.com