Danfoss 068Z3209

Danfoss TEX-2 R-22 TXV Instruction Manual

Modèl: 068Z3209

For 3/8"x1/2" Flare Connections

1. Entwodiksyon

This manual provides essential information for the proper installation, operation, and maintenance of the Danfoss TEX-2 Thermostatic Expansion Valve (TXV) model 068Z3209. This valve is designed for use with R-22 refrigerant in refrigeration and air conditioning systems, featuring 3/8" inlet and 1/2" outlet flare connections.

Proper understanding and adherence to these instructions are crucial for ensuring the longevity, efficiency, and safe operation of the valve and the overall system.

2. Enfòmasyon sou Sekirite

Always observe general safety precautions when working with refrigeration systems. This includes, but is not limited to:

3. Pwodwi souview

The Danfoss TEX-2 TXV (model 068Z3209) is a thermostatic expansion valve designed to regulate the flow of refrigerant into the evaporator, maintaining a constant superheat at the evaporator outlet. This ensures optimal evaporator performance and protects the compressor from liquid refrigerant slugging.

Danfoss TEX-2 TXV with copper strap

Figi 3.1: Plis paseview of the Danfoss TEX-2 TXV, showing the valve body, flare connections, capillary tube, sensing bulb, and a copper strap for bulb attachment.

Close-up of Danfoss TEX-2 TXV label

Figi 3.2: Close-up view of the valve's top plate, displaying model number (068Z3209), refrigerant type (R22/R407C), temperature range (-40/+10°C, -40/+50°F), and pressure ratings (PS 34 bar/MWP 500 psig).

Danfoss TEX-2 TXV product packaging

Figure 3.3: The product packaging for the Danfoss TEX-2 TXV, showing the brand logo, model information, and specifications.

4. Enstalasyon ak Enstalasyon

Proper installation is critical for the correct functioning of the TXV. Follow these steps carefully:

  1. Preparasyon sistèm: Ensure the refrigeration system is clean and free of contaminants. Evacuate the system thoroughly to remove non-condensable gases and moisture.
  2. Plasman Valv: Install the TXV as close as possible to the evaporator inlet. Ensure the valve body is oriented correctly according to the flow arrow.
  3. Connecting Flare Fittings:
    • Clean the flare surfaces on both the valve and the tubing.
    • Apply a small amount of refrigeration oil to the flare surfaces.
    • Align the flare nuts and hand-tighten them.
    • Using two wrenches (one to hold the valve body, one to tighten the nut), tighten the flare nuts to the recommended torque specifications to ensure a leak-free seal. Avoid overtightening.
  4. Enstalasyon anpoul deteksyon an:
    • Mount the sensing bulb horizontally on a clean, bare section of the suction line, immediately after the evaporator outlet.
    • For suction lines up to 7/8" (22mm), mount the bulb on top of the pipe. For larger pipes, mount it at the 4 or 8 o'clock position.
    • Secure the bulb firmly with the provided copper strap or clamps to ensure good thermal contact. Insulate the bulb and the first few inches of the capillary tube to prevent ambient temperature interference.
  5. Tès koule: After installation, pressurize the system with nitrogen and perform a thorough leak test using an electronic leak detector or soap bubbles on all connections.
  6. System Charging: Charge the system with the correct type and amount of R-22 refrigerant according to the system manufacturer's specifications.

5. Prensip Operasyon yo

The Danfoss TEX-2 TXV operates by balancing three forces:

The valve modulates its opening to maintain a constant superheat. When the superheat increases (e.g., due to higher heat load), the bulb temperature rises, increasing P1, which opens the valve further to allow more refrigerant into the evaporator. Conversely, when superheat decreases, P1 drops, and P2 + P3 overcome P1, causing the valve to close slightly, reducing refrigerant flow.

6. Antretyen

The Danfoss TEX-2 TXV is designed for reliable operation with minimal maintenance. However, periodic checks are recommended as part of overall system maintenance:

NAN. Depanaj

If the refrigeration system is not performing optimally, the TXV may be a contributing factor. Here are some common issues and potential causes:

SentòmKòz posibAksyon
High Superheat / Starved Evaporator
  • Undercharge nan febrifuj
  • Clogged filter-drier
  • TXV orifice partially blocked
  • Sensing bulb loose or uninsulated
  • External equalizer line blocked (if applicable)
  • Tcheke chaj febrifuj la
  • Ranplase filtè-secheur a
  • Inspect/clean TXV (if serviceable) or replace
  • Re-secure and insulate bulb
  • Klè blokaj
Low Superheat / Flooded Evaporator
  • Surcharge nan febrifuj
  • Sensing bulb incorrectly positioned or contaminated
  • TXV stuck open
  • Internal leak in TXV
  • Ajiste chaj febrifuj la
  • Reposition/clean bulb
  • Ranplase TXV
  • Ranplase TXV
Fluctuating Superheat
  • Improper bulb contact or insulation
  • Pressure drop across evaporator too high
  • System hunting
  • Re-secure and insulate bulb
  • Check evaporator for restrictions
  • Verify system design and charge

Note: Troubleshooting should only be performed by certified HVAC/R technicians. Incorrect diagnosis or repair can lead to system damage or personal injury.

8. Espesifikasyon

Key specifications for the Danfoss TEX-2 TXV (Model 068Z3209):

9. Garanti ak sipò

For specific warranty terms and conditions, please refer to the official Danfoss warranty policy or contact your authorized Danfoss distributor or reseller. Warranty coverage typically applies to defects in materials and workmanship under normal use and service.

For technical support, product inquiries, or service assistance, please visit the official Danfoss website or contact their customer service department. When contacting support, please have your product model number (068Z3209) and any relevant system details available.

You can find more information about Danfoss products and support at www.danfoss.com.

Dokiman ki gen rapò - 068Z3209

Preview Danfoss Universal TR 6 TXV: Efikasite Enèji ak Ranplasman OEM pou Sistèm HVAC yo
Eksplore valv ekspansyon tèmostatik Danfoss Universal TR 6 la (TXV) pou èkondisyone rezidansyèl ak ponp chalè. Karakteristik yo enkli amelyorasyon efikasite enèji enpòtan, kapasite ranplasman OEM, ak espesifikasyon teknik detaye pou sistèm R-22 ak R-410A yo.
Preview Danfoss Stuffing Box Installation Guide for VFG, VFQ, AFQM Series
Comprehensive installation guide for Danfoss stuffing boxes, including models VFG 22(221), VFQ 22(221), AFQM 2, and AFQMP 2. Provides step-by-step instructions and technical specifications for proper assembly and maintenance.
Preview Gid Enstalasyon Valv Ekspansyon Tèmostatik Danfoss TR6
Gid enstalasyon pou Val Ekspansyon Tèmostatik Danfoss TR6 la, ki kouvri febrifujan, presyon k ap travay, direksyon koule, paramèt, ak espesifikasyon teknik.
Preview Gid Enstalasyon Kontwolè Santral Danfoss Link CC pou Sistèm Chofaj Kay Entelijan
Gid enstalasyon konplè pou Kontwolè Santral Danfoss Link CC a, yon sistèm kontwòl chofaj san fil pwogramasyon pou kay jiska 300 m². Aprann kijan pou enstale, konfigire, epi jere solisyon chofaj kay entelijan ou a, ki gen ladan koneksyon aparèy, konfigirasyon Wi-Fi, ak mizajou lojisyèl.
Preview Enfòmasyon sou garanti pwodwi Danfoss TRV
Detay konplè sou garanti pou seri pwodwi Danfoss Thermostatic Radiator Valves (TRV), ki kouvri tèm garanti estanda 5 ane ak sistèm 10 ane, lis pwodwi, pwosedi reklamasyon, ak esklizyon.
Preview Gid Aplikasyon Tèmosta Danfoss Link™ & Connect pou Kontwòl Chofaj
Gid aplikasyon sa a soti nan Danfoss bay enfòmasyon konplè sou sistèm kontwòl chofaj Danfoss Link™ ak Connect Thermostats yo. Li kouvri konpozan sistèm yo, direktiv jeneral pou ekipman pou chalè ak jesyon chanm, epi li detaye aplikasyon pou chodyè, chodyè santral, chofaj distri, ak ponp chalè, pou optimize efikasite enèji ak konfò nan anviwònman rezidansyèl yo.