EARU EAATS-A Series Dual Power Automatic Transfer Switch (ATS) Instruction Manual

Model: EAATS-A

For optimal performance and safe operation, please read this manual thoroughly before use.

1. Entwodiksyon

The EARU EAATS-A series Automatic Transfer Switch (ATS) is engineered for dual-power supply systems, operating on AC 50/60Hz with rated voltages up to 400V. This device ensures an uninterrupted power supply by automatically switching to a backup power source when the main power supply fails (e.g., due to under-voltage, loss of voltage, or phase failure).

Designed with dual electrical and mechanical interlocks, the ATS prevents simultaneous connection of both power sources, guaranteeing safe and reliable operation. It is an essential component for critical applications in high-rise buildings, hospitals, fire protection systems, and industrial facilities where high power reliability is paramount.

This manual provides detailed instructions for the installation, operation, and maintenance of your ATS unit. Please retain it for future reference.

2. Enstriksyon Sekirite Enpòtan

AVÈTISMAN

The ATS series employs reliable interlocking and automatic monitoring to manage power transfer, ensuring continuous and safe operation. This product does not feature an explosion-proof structure and must not be used in flammable environments, such as those containing flammable gases, liquids, or explosives.

ENFÒMASYON SEKIRITE

  1. Please use this product in accordance with the instructions in this manual.
  2. Pa demonte pwodui sa a poukont ou.
  3. Pay attention to the rated voltage pou itilize.

3. Spécifications pwodwi

The EAATS-A series ATS is available in 2P and 4P configurations, supporting both 110V and 220V AC systems. Key technical parameters are detailed below:

ParamètValè
KaliteMini Circuit breaker, ATS
Nimewo ModèlATS
Rated aktyèl100 A (also available in 10, 16, 20, 25, 32, 40, 50, 63, 80A)
Rated Voltage UeAC220V / AC110V (Operating), AC400V (Design), 50/60Hz
Izolasyon Voltage UiAC690V, 50Hz
Rated Impulse reziste Voltage8kV
Rated Short-Circuit Current ig50kA
Chanje Tan0.008s / 8ms
Lavi elektrik2000 fwa
Lavi Operasyon Manyèl5000 fwa
ATSE ClassPC
SètifikasyonCE
Nimewo Pòl2P, 4P
EstandaIEC60947-6-1

Dimansyon:

  • Width (2P): 108mm (4.25in)
  • Width (4P): 143mm (5.63in)
  • Wotè: 96mm (3.78in)
  • Pwofondè: 76mm (2.99in)
Tablo dimansyon ak paramèt pwodwi yo
Figi 3.1: Dimansyon pwodwi ak paramèt teknik

4. Konpozan ak Kontwòl

The ATS unit features clearly marked terminals and indicators for easy identification and operation.

Detaye view of the ATS components and terminals
Figure 4.1: Main Components and Terminals
  • Main Terminal of Common Power Side (Source A): Connection point for the primary power source.
  • Main Terminal of Standby Power Side (Source B): Connection point for the backup power source.
  • Main Terminal of Load Connection Side: Output terminals for connecting to the electrical load.
  • Manual Switch Handle: Used to manually switch between Source A and Source B.
  • Manual/Automatic Switching Selector: A toggle switch to select between manual and automatic operation modes.
  • Yon endikatè pouvwa: Illuminates when Source A is active.
  • B Power Indicator: Illuminates when Source B is active.
  • Main Power Terminal and Passive Signal (AC220V): Control terminals for Source A.
  • Standby Power Terminal and Passive Signal (AC220V): Control terminals for Source B.

5. Enstalasyon ak fil elektrik

The ATS can be installed vertically in a control cabinet or distribution cabinet. Ensure sufficient distance for proper ventilation and operation. The cross-sectional area of copper wires should not be less than 2.5mm².

According to the installation requirements of your power distribution system, provide appropriate circuit breakers to ensure the safety of staff and equipment.

5.1 Dyagram fil elektrik

Below are typical wiring diagrams for different power source configurations. Always ensure correct polarity and secure connections.

City Grid - Generator Wiring (2P)

Wiring diagram for City Power and Generator (2P configuration)
Figure 5.1: 2P City Grid - Generator Wiring Diagram
  • Common Incoming Line: Connects to the main power source (City Power).
  • Standby Incoming Line: Connects to the backup power source (Generator).
  • Chaj Sòti: Connects to the electrical load.
  • Common Control Line: Control signal from the main power source.
  • Standby Control Line: Control signal from the backup power source.

City Grid - PV Energy Wiring (Solar Energy)

Wiring diagram for City Grid-PV Energy (Solar Energy)
Figure 5.2: City Grid - PV Energy Wiring Diagram

This diagram illustrates the special connection mode for a photovoltaic inverter setup:

  • Photovoltaic Power Station (Main Power Supply A): Connects to the inverter, then to "Normal Power A" input.
  • Standby Power Supply B (City Electricity): Connects to "Reverse Power B" input.
  • Ensure firing lines and zero lines are correctly connected as shown.
  • Output connects to electrical equipment.

Note: The normal/backup power supply needs to be converted into 220V AC through an inverter. However, the inverter is only applicable to the mains-photovoltaic scenario, not the mains-generator and mains-mains scenarios.

City Grid - City Grid Wiring (4P)

Wiring diagram for City Grid-City Grid (4P configuration)
Figure 5.3: 4P City Grid - City Grid Wiring Diagram

This diagram shows a 4-pole connection for two city grid power sources. Ensure R, S, T, N connections are correctly made for both Source A and Source B.

6. Operasyon Enstriksyon

The ATS unit can operate in both manual and automatic modes. The selector switch on the front panel controls the mode of operation.

6.1 Operasyon otomatik

In automatic mode, the ATS continuously monitors the main power supply (Source A). If Source A fails (e.g., under-voltage, loss of voltage, or phase failure), the ATS will automatically switch to the backup power supply (Source B) within milliseconds (0.008s/8ms) to ensure uninterrupted power to the load. When the main power supply is restored, the ATS will automatically switch back to Source A.

Diagram showing the automatic transfer switch logic (Primary Power to Backup Power)
Figure 6.1: Automatic Transfer Logic

The switching logic is as follows:

  1. When the normal power supply is normal, use the normal power supply.
  2. When the normal power supply is cut off, automatically switch to the backup power supply.
  3. When manually set to the "backup position", if the normal power supply is restored, it will still switch back to the normal power supply.
  4. When both the normal power supply and the backup power supply are cut off, even if the photovoltaic power supply has power, it will not switch to the normal power supply.

Note: Manual operation must be in the "Manual" position for manual control.

6.2 Operasyon manyèl

To manually switch between power sources, set the selector switch to the "Manual" position. Then, use the manual switch handle to select either Source A or Source B. This mode is useful for maintenance or testing purposes.

6.3 Videyo Demonstrasyon Pwodwi

Videyo 6.1: Finiview of the EARU ATS unit and its manual.

7. Maintenance, Inspection, and Storage

Regular maintenance ensures the longevity and reliable performance of your ATS unit. All power supplies must be cut off before any inspection or maintenance.

7.1 Inspection Items

  • Check for any damaged or dirty contact parts. Clean any dust or dirt from the case.
  • Verify that there are no burnt metal particles attached to and around the surface.
  • Ensure that the contact surface is clean and free from rust, oxidation, and dirt to maintain good contact.
  • Check for any loose parts or metal pieces.
  • Measure the insulation resistance between normal supply, alternating power supply, load, and metal parts. The insulation resistance should not be less than 10MΩ.

7.2 Depo

The ATS should be stored in an environment equivalent to normal wiring equipment, which is dust-proof, moisture-proof, and corrosion-proof.

7.3 Orè antretyen

  • The first maintenance and inspection should be carried out within 6 months after initial use.
  • Subsequent maintenance and inspections should be performed at least once a year.
  • Increase maintenance frequency in harsh installation conditions.

NAN. Depanaj

If the ATS unit is not functioning as expected, consider the following common issues:

  • No automatic transfer: Ensure the unit is set to "Auto" mode. Check if both power sources are connected and providing the correct voltage. Verify control wiring connections.
  • Power indicators not lighting up: Check the power supply to the control terminals (Main Power Terminal and Standby Power Terminal). Ensure the rated voltage apwovizyone.
  • Unit not switching manually: Ensure the unit is in "Manual" mode. Check for any mechanical obstructions with the manual switch handle.
  • Overheating or unusual smells: Immediately disconnect power from both sources. This could indicate a serious electrical fault. Do not attempt to repair yourself.

If issues persist after basic checks, it is recommended to consult a qualified electrician or contact EARU customer support.

9. Konsèy itilizatè yo

  • Verify Current Rating: Before purchasing or installing, ensure the ATS unit's rated current (e.g., 100A) matches or exceeds the requirements of your electrical system. Different current ratings (e.g., 25A, 63A) may be available for specific needs.
  • Enstalasyon pwofesyonèl rekòmande: Due to the critical nature of power transfer, professional installation by a certified electrician is highly recommended to ensure safety and compliance with local electrical codes.
  • Tès regilye: Periodically test the automatic transfer function by simulating a main power failure to ensure the system is operating correctly.

10. Sipò ak Plis Enfòmasyon

For any questions, technical support, or further information regarding your EARU EAATS-A ATS, please contact the manufacturer directly.

Yon vèsyon elektwonik manyèl itilizatè sa a disponib pou telechaje:

Telechaje Manyèl Itilizatè a (PDF)

This manual is for reference only. Product or version upgrades may occur without notice. The actual product prevails.

Dokiman ki gen rapò - EAATS-A

Preview EARU EAL-2 Din Rail Circuit Breaker Instruction Manual
Instruction manual for the EARU EAL-2 series din rail circuit breaker, detailing its features, safety instructions, and product parameters for AC 2P 230V 4P 400V A Type RCBO RCCB MCB electronic residual current circuit breakers.
Preview EARU KR0548-CH WiFi Smart Automatic Transfer Switch (ATS) User Manual
User manual for the EARU KR0548-CH WiFi Smart Automatic Transfer Switch (ATS). Learn how to install, connect, and operate the device using the EARU app for seamless switching between main and backup power sources.
Preview EARU-X6/8 Metal LED Indicator Light Instruction Manual
User manual for EARU-X6/8 series Metal LED Indicator Lights, detailing safety instructions, warnings, and product description for reliable status indication in industrial and traffic applications.
Preview EARU EAMPManyèl Itilizatè Pwotektè Enèji Entelijan WiFi Seri DW-TY-63 la
Manyèl itilizatè konplè pou EARU E aAMPDW-TY-63 series WiFi Smart Energy Protector, detailing features, installation, app connection, parameter settings, and troubleshooting. Covers over/under voltage, over current, leakage protection, energy monitoring, and remote control.
Preview EARU EAMPManyèl Itilizatè Pwotektè Enèji Entelijan WiFi Seri DW-TY-63 | Volimtage, Kouran, Pwoteksyon kont flit
Manyèl itilizatè konplè pou EARU E aAMPPwotektè Enèji Entelijan WiFi Seri DW-TY-63. Aprann plis sou enstalasyon, karakteristik, espesifikasyon teknik, kontwòl aplikasyon ak depanaj pou vol.tage, kouran, ak pwoteksyon kont flit.
Preview EARU EAPDX-40/63 Series Adjustable VoltagManyèl Itilizatè Pwotektè Kouran ak E
User manual for the EARU EAPDX-40/63 Series Adjustable Voltage & Current Protector, detailing specifications, features, and operation for electrical protection. Includes setup instructions and parameter configuration.