GODIYMODULES Standard Edition

GODIYMODULES Digital Display Meter Standard Edition User Manual

Model: Standard Edition

1. Entwodiksyon

This manual provides comprehensive instructions for the installation, operation, and maintenance of the GODIYMODULES Digital Display Meter, Standard Edition. This universal analog input display meter is designed to work with various sensors that provide analog output, such as temperature transmitters, frequency converters, motor speed sensors, pressure transducers, and liquid level sensors. Please read this manual thoroughly before operating the device to ensure correct usage and optimal performance.

2. Pwodwi souview

The GODIYMODULES Digital Display Meter is a versatile panel meter capable of displaying actual physical quantities based on analog input signals. It supports both current and voltage inputs, with default adaptations for 0-10V, 2-10V, 0-20mA, and 4-20mA. The meter features a 0.55-inch 4-digit digital tube display for clear readings and intuitive button controls for parameter settings.

Devan view of the GODIYMODULES Digital Display Meter

Figi 2.1: Devan view of the GODIYMODULES Digital Display Meter, showing the digital display and control buttons.

3. Karakteristik kle

  • Universal Analog Input: Compatible with 0-10V, 2-10V, 0-20mA, and 4-20mA signals. Adaptable to other ranges via polarization and gain parameters.
  • Wide Power Supply Range: DC6~25V for standard and RS485 versions; DC8~25V for relay output version.
  • Pwoteksyon pouvwa: Features anti-reverse connection and surge protection.
  • Single Analog Input: Supports either voltage oswa aktyèl opinyon.
  • Enpedans Antre: >30kΩ for voltage type, <250Ω for current type.
  • Ekspozisyon klè: 0.55 inch, 4-digit digital tube display.
  • Easy Parameter Setting: Built-in buttons for convenient configuration.
  • Konsepsyon kontra enfòmèl ant: Mechanical size of 79 x 43 x 25 mm, with an installation opening of 76.5 x 39.5 mm.
  • Optional RS485 Interface: (Available in RS485 version) Supports Modbus-RTU protocol for multi-meter communication.
  • Optional Relay Output: (Available in relay output version) One normally open relay output, load capacity: 3A30VDC/3A250VAC.

4. Enstalasyon

4.1. Enstalasyon mekanik

The meter is designed for panel mounting. Ensure the installation opening in your panel matches the specified dimensions.

  • Gwosè mekanik: 79 mm (Length) x 43 mm (Width) x 25 mm (Depth)
  • Ouvèti enstalasyon: 76.5 mm (Length) x 39.5 mm (Width)
Anlè angilè view of the meter showing buttons and terminal block

Figi 4.1: Anlè angilè view of the meter, illustrating the physical form factor and button layout.

Angle view of the meter showing buttons and terminal block from another perspective

Figi 4.2: Yon lòt angilè view of the meter, providing a clearer look at the control buttons and terminal block.

4.2. Enstriksyon fil elektrik

Refer to the common wiring diagram for proper connection of power supply and analog input. Ensure the power supply voltage is within the specified range to prevent damage.

Retounen view of the meter with wiring diagram and terminal labels

Figi 4.3: Retounen view of the meter showing the wiring diagram for power, ground, and analog input terminals.

Deskripsyon tèminal:

  • PWR: Positive power supply input (DC6~25V for standard/RS485, DC8~25V for relay version).
  • GND: Ground connection for power supply and analog input.
  • AI: Analog Voltage Input (0-10V, 2-10V).
  • mA: Analog Current Input (0-20mA, 4-20mA).
  • NC: Not Connected.
  • RS485 (R, T, S): For RS485 communication (available in RS485 version only). R indicates data reception, T indicates data transmission, S indicates signal ground.
  • Relay (NO): Normally Open relay output (available in relay output version only).

Enpòtan: The meter supports either voltage input (AI) or current input (mA), but not both simultaneously. Connect your sensor output to the appropriate terminal.

5. Operasyon Enstriksyon

5.1. Button Functions and Display States

The meter features four buttons for navigation and parameter adjustment: SET, UP (↑), DOWN (↓), and OK. The 4-digit digital display shows the measured value or parameter settings.

Fonksyon bouton:

  • Mete: Enters parameter setting mode or cycles through parameter groups.
  • UP (↑): Increases value or navigates up in menus.
  • DOWN (↓): Decreases value or navigates down in menus.
  • OK: Confirms selection or saves parameter changes.

Digital Tube Display State Transition Diagram:

The meter typically displays the measured value. Pressing the SET button allows entry into the parameter setting menu. Use UP/DOWN to navigate and OK to select/confirm. Pressing SET again will exit the parameter setting mode or move to the next parameter group.

5.2. Paramèt Anviwònman

The meter's functionality is configured through various parameters organized into groups. To enter the parameter setting mode, press the SET bouton. Sèvi ak la UP epi DESANN bouton pou ajiste valè yo ak OK pou konfime. Peze SET to move between parameters or exit.

5.2.1. F0-0 Displayed Quantity Collection Parameters

ParamètScope and DescriptionDefoLi/Ekri
F0-0Displayed value monitoring: Displays the current collected value. Range: 0-100.0%0.0Li sèlman
F0-1Display accuracy: The number of decimal places displayed in the collected value. Range: 0-31Li/Ekri
F0-2Show minimum: The minimum value corresponding to "acquisition value" 0%. Range: -9999 to 99990Li/Ekri
F0-3Show maximum: The maximum value corresponding to the "acquisition value" is 100%. Range: -9999 to 99991000Li/Ekri
F0-4Display range: The display range is F0-2 to F0-3. Starting from F0-2.0Li/Ekri

Nòt: The displayed value is a default percentage. You can set your own display range using F0-2 to F0-4.

5.2.2. F1-0 Parameter Group Configuration Parameters

ParamètScope and DescriptionDefoLi/Ekri
F1-0Input type selection: 0: 0-10V or 0-20mA (corresponds to 0-100% of the acquisition value). 1: 2-10V or 4-20mA (corresponds to 0-100% of the acquisition value).0Li/Ekri
F1-1Input filter time: The filtering time for the input signal. Range: 0-1000ms.200Li/Ekri
F1-2Input offset: The offset value for the input signal. Range: 0-100.0%0.0Li/Ekri
F1-3Input gain: The gain value for the input signal. Range: 0-100.0%100.0Li/Ekri
F1-4Drop detection threshold: If the input value is not detected, the display will show "----". This parameter sets the threshold for detection. If the input value is less than this threshold, it is considered not detected. Range: 0-100.0% (Starting from V0.10)0.0Li/Ekri

Nòt: By setting the polarization parameter (F1-2) and gain parameter (F1-3), the meter can be adapted to other input ranges within 0-10V or 0-20mA.

5.2.3. F2-0 Parameter Group Relay Output Parameters (for Relay Output Version)

ParamètScope and DescriptionDefoLi/Ekri
F2-0Relay output: 0: Normally open, 1: Normally closed.0Li/Ekri
F2-1Condition type: 0: Greater than comparison value 1, 1: Less than comparison value 1, 2: Greater than comparison value 2, 3: Less than comparison value 2.0Li/Ekri
F2-2Comparison value 1: The value used for comparison. Range: 0-100.0%50.0Li/Ekri
F2-3Comparison value 2: The value used for comparison. Range: 0-100.0%0.0Li/Ekri
F2-4Hysteresis interval: The hysteresis value to prevent frequent relay operation. Range: 0-100.0%5.0Li/Ekri
F2-5Relay status when offline: 0: Keep current status, 1: When the offline value is less than the comparison value, the relay is closed, 2: When the offline value is greater than the comparison value, the relay is closed.0Li/Ekri

Nòt: These parameters are only applicable to the version of the meter equipped with a relay output. The Standard Edition may not include this feature.

5.3. RS485 Communication Parameters (for RS485 Version)

This section applies only to the Digital Display Meter with RS485 interface. It uses the standard Modbus-RTU protocol for communication.

Detailed diagram showing parameter settings for F0, F1, F2, and RS485 communication

Figi 5.1: Comprehensive parameter tables including F0, F1, F2, and RS485 communication settings.

ParamètScope and DescriptionDefoLi/Ekri
F7-0Local address: The address of the meter in the Modbus network. Range: 1-2471Li/Ekri
F7-1Baud rate: 0: 1200bps, 1: 2400bps, 2: 4800bps, 3: 9600bps, 4: 19200bps, 5: 38400bps.3Li/Ekri
F7-2Data format: 0: 8N1 (8 data bits, 1 stop bit, no parity), 1: 8E1 (8 data bits, 1 stop bit, even parity), 2: 8O1 (8 data bits, 1 stop bit, odd parity), 3: 8N2 (8 data bits, 2 stop bits, no parity).0Li/Ekri
F7-3Response delay: The delay time before the meter responds to a Modbus query. Used to prevent bus collisions in half-duplex communication. Range: 0-100ms.5Li/Ekri
F7-4Communication type: 0: The display table is in the network host mode, 1: The display table is in the network slave mode, 2: The display table through the broadcast mode.0Li/Ekri
F7-5Parameter interval: The interval time for the meter to send parameters. Range: 0-1000ms.100Li/Ekri
F7-6Send recovery time: The time for the meter to send recovery parameters. Range: 0-1000ms.100Li/Ekri
F7-7Software version number: Displays the current software version.1.00Li sèlman

Modbus-RTU Protocol Details:

The meter supports standard Modbus-RTU protocol. The communication parameters (address, baud rate, data format) must be configured correctly to match the master device. The image also shows a table of Modbus register addresses for various parameters (e.g., F0-0, F0-1, F1-0, etc.) which can be read or written via Modbus commands.

For detailed Modbus register addresses and functions, refer to the provided diagram (Figure 5.1) or the official Modbus communication guide for this device. Example: To read F0-0, use Modbus function code 03 (Read Holding Registers) with the corresponding address.

6. Antretyen

  • Netwayaj: Sèvi ak yon twal mou epi sèk pou netwaye ekran mèt la ak casing. Pa sèvi ak pwodui netwayaj abrazif oswa solvan.
  • Anviwònman: Ensure the meter is operated within its specified environmental conditions (temperature, humidity) to prolong its lifespan.
  • Koneksyon: Periodically check all wiring connections for tightness and ensure they are free from corrosion.
  • Kalibrasyon: If accuracy issues are suspected, refer to the parameter settings for input offset and gain adjustment, or consult a qualified technician for recalibration.

NAN. Depanaj

PwoblèmKòz posibSolisyon
Kontè a pa limen.Pa gen ekipman pou kouran oswa vòltaj ki pa kòrèktage.Check power connections and ensure voltage is within DC6~25V (or DC8~25V for relay version).
Display shows "----".No analog input signal detected or signal below F1-4 threshold.Verify sensor connection and output. Check F1-4 (Drop detection threshold) setting.
Incorrect readings.Incorrect input type (F1-0), offset (F1-2), or gain (F1-3) settings. Sensor malfunction.Review F1-0, F1-2, F1-3 parameters. Check sensor calibration and output.
Echèk kominikasyon RS485.Incorrect RS485 parameters (F7-0 to F7-4). Wiring issues.Verify F7-0 (Local address), F7-1 (Baud rate), F7-2 (Data format) match the master device. Check RS485 wiring (R, T, S).

8. Espesifikasyon

MakMODIL BONDYE
ModèlEdisyon estanda
Kalite Siyal AntreVoltage (0-10V, 2-10V), Current (0-20mA, 4-20mA)
Power Supply (Standard/RS485)DC6 ~ 25V
Power Consumption (Standard/RS485)24V/40mA
Power Supply (Relay Output Version)DC8 ~ 25V
Power Consumption (Relay Output Version)24V/50mA
Input Impedance (Voltage Type)> 30kΩ
Input Impedance (Current Type)<250Ω
Ekspozisyon0.55 inch, 4-digit digital tube
Gwosè mekanik79 x 43 x 25 mm
Ouvèti enstalasyon76.5 x 39.5 mm
Pwa50 g
RS485 Protocol (Optional)Modbus-RTU
Sòti relè (Si ou vle)1 Normally Open, 3A30VDC/3A250VAC